How Many BTU Do I Need?
For one room, start with the ENERGY STAR sizing chart, which matches room area to air conditioner capacity for 8 ft ceilings. The extra columns show what to actually buy, because window units, portable units and mini-splits come in different sizes.
| Room area (sq ft) | BTU/h needed | Window AC to buy | Portable (SACC) | Mini-split head |
|---|---|---|---|---|
| 100–150 | 5,000 | 5,000 | 5,000 | 6,000 |
| 150–250 | 6,000 | 6,000 | 6,000 | 6,000 |
| 250–300 | 7,000 | 8,000 | 7,000 | 9,000 |
| 300–350 | 8,000 | 8,000 | 8,000 | 9,000 |
| 350–400 | 9,000 | 10,000 | 9,000 | 9,000 |
| 400–450 | 10,000 | 10,000 | 10,000 | 12,000 |
| 450–550 | 12,000 | 12,000 | 12,000 | 12,000 |
| 550–700 | 14,000 | 14,000 | 14,000 | 18,000 |
| 700–1,000 | 18,000 | 18,000 | — | 18,000 |
| 1,000–1,200 | 21,000 | 24,000 | — | 24,000 |
| 1,200–1,400 | 23,000 | 24,000 | — | 24,000 |
| 1,400–1,500 | 24,000 | 24,000 | — | 24,000 |
| 1,500–2,000 | 30,000 | 2 units or central | — | 30,000 |
| 2,000–2,500 | 34,000 | 2 units or central | — | 36,000 |
Then adjust (ENERGY STAR’s rules): take off 10% for a heavily shaded room, add 10% for a very sunny one, add 600 BTU for each person beyond two who regularly uses the room, and add 4,000 BTU for a kitchen. Example: a 320 sq ft living room used by four people needs 8,000 + 1,200 = 9,200 BTU/h, so a 10,000 BTU window unit. A 12 × 14 ft bedroom that gets afternoon sun needs 6,000 × 1.1 = 6,600, so 8,000 BTU. We also scale for ceilings over 8 ft (a 10 ft ceiling adds 25%).
What Size Room Does Each AC Size Cool?
What size room does a 5,000 BTU air conditioner cool?
About 100–150 sq ft with 8 ft ceilings and normal sun. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 5,000 BTU on the SACC rating (about 7,100 on the older ASHRAE scale).
What size room does a 6,000 BTU air conditioner cool?
About 150–250 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 150 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 6,000 BTU on the SACC rating (about 8,600 on the older ASHRAE scale).
What size room does a 8,000 BTU air conditioner cool?
About 250–350 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 300 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 8,000 BTU on the SACC rating (about 11,400 on the older ASHRAE scale).
What size room does a 10,000 BTU air conditioner cool?
About 350–450 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 400 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 10,000 BTU on the SACC rating (about 14,300 on the older ASHRAE scale).
What size room does a 12,000 BTU air conditioner cool?
About 450–550 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 450 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 12,000 BTU on the SACC rating (about 17,100 on the older ASHRAE scale).
What size room does a 14,000 BTU air conditioner cool?
About 550–700 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 550 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 14,000 BTU on the SACC rating (about 20,000 on the older ASHRAE scale).
What size room does a 18,000 BTU air conditioner cool?
About 700–1,000 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 700 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 18,000 BTU on the SACC rating (about 25,700 on the older ASHRAE scale).
What size room does a 24,000 BTU air conditioner cool?
About 1,000–1,500 sq ft with 8 ft ceilings and normal sun. In a very sunny room, plan on up to about 1,200 sq ft. Add 600 BTU for each regular occupant beyond two, and 4,000 for a kitchen, so those rooms need a bigger unit. For a portable AC, look for 24,000 BTU on the SACC rating (about 34,300 on the older ASHRAE scale).
BTU Per Square Foot: Rules of Thumb by Climate
Whole-home rules of thumb depend heavily on climate and how well the house holds heat. These are the factors the calculator uses for whole homes (8 ft ceilings, normal sun). They are our rule-of-thumb calibration, not a published standard: an average 2,000 sq ft home in zone 4 comes out at 3.7 tons, in line with the common 500–600 sq ft per ton rule.
| Cooling | Example cities | Poor | Average | Good | High-perf. |
|---|---|---|---|---|---|
| Zone 1 | Miami, Honolulu | 36 | 30 | 26 | 21 |
| Zone 2 | Houston, Phoenix, Orlando | 32 | 27 | 23 | 19 |
| Zone 3 | Atlanta, Dallas, Los Angeles | 30 | 25 | 21 | 18 |
| Zone 4 | Washington DC, St. Louis, Seattle | 26 | 22 | 19 | 15 |
| Zone 5 | Chicago, Denver, Boston | 24 | 20 | 17 | 14 |
| Zone 6 | Minneapolis, Burlington VT | 22 | 18 | 15 | 13 |
| Zone 7 | Duluth, northern Maine | 19 | 16 | 14 | 11 |
| Heating | Design temp | Poor | Average | Good | High-perf. |
|---|---|---|---|---|---|
| Zone 1 | 45 °F | 12 | 9 | 6 | 4 |
| Zone 2 | 30 °F | 20 | 14 | 10 | 7 |
| Zone 3 | 22 °F | 24 | 17 | 12 | 9 |
| Zone 4 | 12 °F | 29 | 20 | 14 | 10 |
| Zone 5 | 0 °F | 35 | 24 | 18 | 13 |
| Zone 6 | -10 °F | 40 | 28 | 20 | 14 |
| Zone 7 | -20 °F | 45 | 32 | 22 | 16 |
When the rule of thumb is wrong
- Lots of glass, or west-facing rooms: afternoon sun through windows can add thousands of BTU. Use “very sunny”, or size one step up.
- High or vaulted ceilings: more air and more wall; the calculator scales by height.
- Open-plan spaces: size for the whole open area, not the “room” you’re standing in.
- Finished attics and bonus rooms over garages: they gain heat from the roof and lose it to the garage; treat insulation as one level worse unless you know it’s good.
- Very tight new homes: loads can be half the old rules; a Manual J often lands at 800–1,000 sq ft per ton.
What Size AC Do I Need for My House?
Estimated cooling load in tons, and the standard size to buy, for an average-insulated home with 8 ft ceilings. One ton is 12,000 BTU/h.
| Home | Zone 1 | Zone 2 | Zone 3 | Zone 4 | Zone 5 | Zone 6 | Zone 7 |
|---|---|---|---|---|---|---|---|
| 1,000 sq ft | 2.5 → 2.5 | 2.2 → 2.5 | 2.1 → 2 | 1.8 → 2 | 1.7 → 2 | 1.5 → 1.5 | 1.3 → 1.5 |
| 1,500 sq ft | 3.8 → 4 | 3.4 → 3.5 | 3.1 → 3.5 | 2.8 → 3 | 2.5 → 2.5 | 2.2 → 2.5 | 2.0 → 2 |
| 2,000 sq ft | 5.0 → 5 | 4.5 → 5 | 4.2 → 4 | 3.7 → 4 | 3.3 → 3.5 | 3.0 → 3 | 2.7 → 3 |
| 2,500 sq ft | 6.2 → 2 × 3 | 5.6 → 5 | 5.2 → 5 | 4.6 → 5 | 4.2 → 4 | 3.8 → 4 | 3.3 → 3.5 |
| 3,000 sq ft | 7.5 → 2 × 4 | 6.8 → 2 × 3.5 | 6.2 → 2 × 3 | 5.5 → 5 | 5.0 → 5 | 4.5 → 5 | 4.0 → 4 |
What Size Furnace Do I Need?
Furnaces are sold by input; what heats the house is the output, input × efficiency (AFUE). A 60,000 BTU furnace at 95% AFUE delivers 57,000 BTU/h; at 80%, 48,000. The ACCA Manual S standard keeps furnace output between 100% and 140% of the heat loss.
| Home | Zone 3 | Zone 4 | Zone 5 | Zone 6 | Zone 7 |
|---|---|---|---|---|---|
| 1,000 sq ft | 16.8k → 40k / 40k | 20.3k → 40k / 40k | 24.5k → 40k / 40k | 28.0k → 40k / 40k | 31.5k → 40k / 40k |
| 1,500 sq ft | 25.2k → 40k / 40k | 30.4k → 40k / 40k | 36.8k → 40k / 60k | 42.0k → 45k / 60k | 47.2k → 60k / 60k |
| 2,000 sq ft | 33.6k → 40k / 45k | 40.6k → 45k / 60k | 49.0k → 60k / 70k | 56.0k → 60k / 70k | 63.0k → 70k / 80k |
| 2,500 sq ft | 42.0k → 45k / 60k | 50.8k → 60k / 70k | 61.2k → 70k / 80k | 70.0k → 80k / 90k | 78.8k → 90k / 100k |
| 3,000 sq ft | 50.4k → 60k / 70k | 60.9k → 70k / 80k | 73.5k → 80k / 100k | 84.0k → 90k / 110k | 94.5k → 100k / 120k |
Why Bigger Isn’t Better
The most common sizing mistake is buying too big. An oversized air conditioner cools the air fast and shuts off before it has pulled much moisture out, so the room hits the thermostat setting but feels cold and clammy. It also starts and stops more often, which wastes energy and wears the compressor. That’s why the ACCA Manual S standard, which building codes reference for new systems, limits a single-stage central AC to 115% of the calculated cooling load (125% for heat pumps), and furnaces to 140% of the heat loss.
Portable AC Ratings: SACC vs ASHRAE
Portable air conditioners often show two BTU numbers. The older ASHRAE rating was measured in conditions that flatter portables; the Department of Energy’s newer SACC (Seasonally Adjusted Cooling Capacity) rating accounts for the heat that leaks back in through the hose and case, and runs roughly 30% lower. Size a portable by its SACC number, and assume a single number on a recent box is SACC.
| ASHRAE (box) | SACC (approx.) |
|---|---|
| 8,000 | ≈ 5,600 |
| 10,000 | ≈ 7,000 |
| 12,000 | ≈ 8,400 |
| 14,000 | ≈ 9,800 |
Heating a Single Room
Electric heaters turn every watt into 3.412 BTU/h, so a 1,500 W plug-in heater, the usual maximum for plug-in heaters, gives about 5,100 BTU/h. Average insulation, 8 ft ceilings:
| Room | Zone 3 (22 °F) | Zone 5 (0 °F) |
|---|---|---|
| 100 sq ft | 492 W (1 × 1,500 W) | 718 W (1 × 1,500 W) |
| 150 sq ft | 739 W (1 × 1,500 W) | 1,077 W (1 × 1,500 W) |
| 200 sq ft | 985 W (1 × 1,500 W) | 1,436 W (1 × 1,500 W) |
| 300 sq ft | 1,477 W (1 × 1,500 W) | 2,154 W (2 × 1,500 W) |
| 400 sq ft | 1,970 W (2 × 1,500 W) | 2,872 W (2 × 1,500 W) |
For a room you heat all winter, a ductless mini-split heat pump costs roughly a third as much to run as resistance heaters, and it cools in summer too.
BTU Conversions
1 ton = 12,000 BTU/h · 1 kW = 3,412 BTU/h · 1 W = 3.412 BTU/h · 1 therm = 100,000 BTU.
| BTU/h | Tons | kW | Watts |
|---|---|---|---|
| 5,000 | 0.42 | 1.47 | 1,465 |
| 6,000 | 0.50 | 1.76 | 1,758 |
| 8,000 | 0.67 | 2.34 | 2,345 |
| 10,000 | 0.83 | 2.93 | 2,931 |
| 12,000 | 1.00 | 3.52 | 3,517 |
| 18,000 | 1.50 | 5.28 | 5,275 |
| 24,000 | 2.00 | 7.03 | 7,034 |
| 36,000 | 3.00 | 10.55 | 10,551 |
| 48,000 | 4.00 | 14.07 | 14,068 |
| 60,000 | 5.00 | 17.58 | 17,585 |
When to Get a Manual J
A Manual J is the room-by-room load calculation HVAC designers use (ACCA’s standard), and the International Residential Code requires equipment to be sized from it with Manual S. Ask for one when you replace a central system, build or add on, or have rooms that are always too hot or cold. A good contractor will give you the report, showing the heating and cooling loads; compare it with this calculator. If a quote is far above both, ask why.
BTU FAQ
Method and Sources
Rooms: the ENERGY STAR room air conditioner sizing chart and its adjustments (shade −10%, sun +10%, +600 BTU per person beyond two, +4,000 for kitchens); scaling for ceilings over 8 ft is ours. Whole homes: cooling = area × zone factor × insulation factor × sun × ceiling ÷ 8; heating = area × heat-loss factor × ceiling ÷ 8 × (70 °F − design temperature). The zone and insulation factors are our own rule-of-thumb calibration and are shown in the tables above. Equipment limits: ACCA Manual S (cooling 95–115% for single-stage AC, up to 125% for heat pumps; furnace output 100–140%). Portable ratings: DOE SACC.
- ENERGY STAR: room air conditioner sizing chart
- HVAC design review form: ACCA Manual S sizing limits (IRC M1401.3)
- Contracting Business: An introduction to ACCA Manual S
- TCL: portable AC ASHRAE and SACC ratings
- DOE Building America: climate zone lookup by county or ZIP
Written by K. Lynch. See our methodology. Spotted a problem with a result? Tell us (include the result link). Updates: Nov 2026, launched.