Wire Size Calculator

For a 120 or 240 V circuit, use 14 AWG copper for 15 A, 12 AWG for 20 A, 10 AWG for 30 A, 8 AWG for 40 A and 6 AWG for 50 A. Runs over about 50 ft at 120 V, or 100 ft at 240 V, may need a bigger size for voltage drop.

Wire size calculator

What are you wiring? (sets typical values; edit anything)

Size the wire from
From the panel to the load, along the route the wire will take.
Material
Advanced: terminals, heat, conduit fill, service rule
Look for “60/75 °C” on the breaker or the equipment label.
Attics and sunny rooftops run hot. Leave blank for 86 °F (30 °C).
Don’t count the ground. Four or more reduce the rating.
Drop is worked out at the full breaker rating unless you enter the real load.
EV chargers and water heaters count as continuous: the breaker and wire are sized at 125%.
Lets 100–400 A dwelling services use the 83% rule (NEC 310.12).
120/240 V appliances like dryers and ranges do; most 240 V-only loads don’t.

Recommended wire

—

Breaker
Ground wire
Ask for
Voltage drop
Voltage at the load
Longest run for this wire

Ratings from NEC Table 310.16; drop from Chapter 9 Table 8 resistance at 75 °C.
SizeRatedDropResult

Check voltage drop in detail →

Check before you wire. Based on the 2023 National Electrical Code. Your city or state may use a different edition or local amendments, and electrical work usually needs a permit. Have a licensed electrician do the work or check it.

Hiring it out? Compare prices from licensed local electricians. Free, no obligation.

How to Choose the Right Wire Size

Wire size depends on four things: the breaker (or the load), the type of wire and how it’s installed, the material, and the distance. The breaker sets the minimum: the wire must be rated for at least the breaker’s amps, so a fault trips the breaker before the wire overheats. Distance can then push the size up, because long runs lose voltage.

BreakerNM-B (Romex) copperTHHN copper in conduitAluminum (XHHW-2/SER)Longest run, 120 VLongest run, 240 V
15 A14 AWG14 AWG—39 ft78 ft
20 A12 AWG12 AWG—46 ft93 ft
30 A10 AWG10 AWG8 AWG49 ft99 ft
40 A8 AWG8 AWG8 AWG57 ft115 ft
50 A6 AWG8 AWG6 AWG73 ft146 ft
60 A4 AWG6 AWG4 AWG97 ft194 ft
70 A4 AWG4 AWG3 AWG83 ft166 ft
80 A3 AWG4 AWG2 AWG91 ft183 ft
90 A2 AWG3 AWG2 AWG103 ft206 ft
100 A— (use SER)3 AWG1 AWG116 ft233 ft
THHN assumes 75 °C terminals. Longest run = 3% voltage drop at the full breaker rating, for the NM-B size. NM-B isn’t made larger than 2 AWG.

Jump to:15 A20 A30 A40 A50 A60 A100 A service200 A service

What Size Wire for Each Breaker

Each answer below gives the size for a short run, then how it grows with distance at the full breaker rating and a 3% drop. Enter your own distance and load above for an exact answer.

What Size Wire for 15 Amps?

14 AWG copper for a 15 A breaker, in NM-B cable or THHN in conduit. Typical uses: lighting and general-purpose outlets.

One-way distanceNM-B, 120 VNM-B, 240 VTHHN in conduit, 240 V
50 ft12 AWG14 AWG14 AWG
100 ft8 AWG12 AWG12 AWG
150 ft8 AWG10 AWG10 AWG
200 ft6 AWG8 AWG8 AWG
300 ft4 AWG8 AWG8 AWG

What Size Wire for 20 Amps?

12 AWG copper for a 20 A breaker, in NM-B cable or THHN in conduit. Typical uses: kitchen, bathroom, laundry and garage outlets; most window air conditioners.

One-way distanceNM-B, 120 VNM-B, 240 VTHHN in conduit, 240 V
50 ft10 AWG12 AWG12 AWG
100 ft8 AWG10 AWG10 AWG
150 ft6 AWG8 AWG8 AWG
200 ft4 AWG8 AWG8 AWG
300 ft3 AWG6 AWG6 AWG

What Size Wire for 30 Amps?

10 AWG copper for a 30 A breaker, in NM-B cable or THHN in conduit. Typical uses: electric dryers, smaller water heaters, wall ovens, rv 30 a pedestals (120 v).

One-way distanceNM-B, 120 VNM-B, 240 VTHHN in conduit, 240 V
50 ft8 AWG10 AWG10 AWG
100 ft6 AWG8 AWG8 AWG
150 ft4 AWG8 AWG8 AWG
200 ft3 AWG6 AWG6 AWG
300 ft2 AWG4 AWG4 AWG

What Size Wire for 40 Amps?

8 AWG copper for a 40 A breaker, in NM-B cable or THHN in conduit. Typical uses: electric ranges and cooktops, 32 a ev chargers.

One-way distanceNM-B, 240 VTHHN in conduit, 240 V
50 ft8 AWG8 AWG
100 ft8 AWG8 AWG
150 ft6 AWG6 AWG
200 ft4 AWG4 AWG
300 ft3 AWG3 AWG

What Size Wire for 50 Amps?

6 AWG copper in NM-B cable (rated 55 A in the 60 °C column), or 8 AWG copper THHN in conduit with 75 °C terminals (50 A). Typical uses: large ranges, hot tubs, rv 50 a pedestals, welders.

Is 8 gauge OK on a 50 amp breaker? Yes for THHN/THWN-2 wires in conduit when the breaker and the equipment are both rated 75 °C; no for NM-B, where 8 AWG is limited to 40 A. That’s why forum answers disagree: both sides are right for different wire.

One-way distanceNM-B, 240 VTHHN in conduit, 240 V
50 ft6 AWG8 AWG
100 ft6 AWG6 AWG
150 ft4 AWG4 AWG
200 ft4 AWG4 AWG
300 ft2 AWG2 AWG

What Size Wire for 60 Amps?

4 AWG copper in NM-B cable (rated 70 A in the 60 °C column), or 6 AWG copper THHN in conduit with 75 °C terminals (65 A). Typical uses: 48 a ev chargers, small sub-panels, tankless water heaters.

Strictly, NM-B on a 60 A breaker needs 4 AWG. 6 AWG NM-B is rated 55 A, and NEC 240.4(B) may allow it on a 60 A breaker for a single appliance. Ask your electrician; the calculator doesn’t apply it.

One-way distanceNM-B, 240 VTHHN in conduit, 240 V
50 ft4 AWG6 AWG
100 ft4 AWG6 AWG
150 ft4 AWG4 AWG
200 ft3 AWG3 AWG
300 ft2 AWG2 AWG

What Size Wire for 100 Amp Service?

4 AWG copper or 2 AWG aluminum for a 100 A single-family service entrance. The NEC lets these wires carry 83% of the rating (83 A), and 4 AWG copper is rated 85 A, 2 AWG aluminum 90 A, at 75 °C.

A 100 A feeder to a sub-panel that doesn’t carry the whole house can’t use the 83% rule: it needs 3 AWG copper or 1 AWG aluminum, and more over long distances:

One-way distanceCopper THHN, 240 VAluminum SER, 240 V
50 ft3 AWG1 AWG
100 ft3 AWG1 AWG
150 ft2 AWG1/0 AWG
200 ft1 AWG2/0 AWG
300 ft2/0 AWG4/0 AWG

What Size Wire for 200 Amp Service?

2/0 AWG copper or 4/0 AWG aluminum for a 200 A single-family service entrance. The NEC lets these wires carry 83% of the rating (166 A), and 2/0 AWG copper is rated 175 A, 4/0 AWG aluminum 180 A, at 75 °C.

A 200 A feeder to a sub-panel that doesn’t carry the whole house can’t use the 83% rule: it needs 3/0 AWG copper or 250 kcmil aluminum, and more over long distances:

One-way distanceCopper THHN, 240 VAluminum SER, 240 V
50 ft3/0 AWG250 kcmil
100 ft3/0 AWG250 kcmil
150 ft3/0 AWG250 kcmil
200 ft3/0 AWG250 kcmil
300 ft250 kcmil400 kcmil

Why the Same Breaker Can Need Two Different Wire Sizes

Every wire size has three current ratings in NEC Table 310.16, one for each insulation temperature: 60, 75 and 90 °C. Which one you may use depends on the weakest link. NM-B cable (Romex) is always held to the 60 °C rating (NEC 334.80), even though the wires inside are rated 90 °C. Individual wires in conduit can use the 75 °C rating, but only if the breaker and the equipment at the other end are marked 75 °C (NEC 110.14(C)). The 90 °C rating is only a starting point when you have to derate for heat or crowded conduit.

Why 8 AWG copper passes or fails on a 50 amp breaker8 AWG copper is rated 40 amps in the 60 degree column used for NM-B cable, 50 amps in the 75 degree column used for THHN in conduit with 75 degree terminals, and 55 amps at 90 degrees, which is only a starting point for derating. Only the 75 degree rating reaches the 50 amp breaker.8 AWG copper: one wire, three ratings60 °C · NM-B (Romex), UF40 A✗ fails on 50 A75 °C · THHN in conduit, 75 °C terminals50 A✓ passes on 50 A90 °C · starting point for derating only55 A50 A breaker
That’s the whole “is 8 gauge OK on 50 amps?” argument: the same 8 AWG copper is 40 A in NM-B and 50 A as THHN in conduit with 75 °C terminals.

The calculator asks for the wire type for this reason, and shows which rule decided the size under every answer.

Long Runs: When Distance Decides the Wire Size

A wire can be big enough not to overheat and still too small for its length. Every foot adds resistance, and the voltage lost in the wire is voltage your equipment doesn’t get. The NEC recommends keeping that drop under 3% on a branch circuit and 5% in total (an informational note, not a rule), and it’s a sensible target for motors, chargers and anything with electronics.

One-way length versus round tripA panel on the left feeds a load on the right 100 feet away. Current flows out on the hot wire and back on the neutral, so the wire is 200 feet of round trip. Calculators ask for the one-way length and double it. Panel Load hot: current out →← neutral: current back one-way length L = 100 ft (enter this) · wire carrying current = 2 × L The drop happens on both wires, which is where the “2” in the formula comes from
Enter the one-way distance. The current goes out on one wire and back on the other, so the formula counts the length twice.

Example: a 50 A RV pedestal 300 ft from the house. 8 AWG copper carries 50 A, but over that distance it would lose far more than 3%. The calculator steps up one size at a time and lands on 2 AWG copper (2.4%) or 1/0 AWG aluminum (2.5%). The size ladder under the result shows the size below failing and the size above passing more easily.

Upsized the wire? Upsize the ground too. When wire is made bigger for voltage drop, NEC 250.122(B) requires the ground wire to grow by the same proportion. The calculator does this for you; many guides forget it.

AWG Wire Size Chart

Diameter is for the bare conductor (solid equivalent). Ampacity is NEC 2023 Table 310.16 at 30 °C (86 °F) with no more than three current-carrying wires together; resistance is Chapter 9 Table 8 at 75 °C, in ohms per 1,000 ft.

SizeDia. (in)Dia. (mm)Area (cmil)Area (mm²)Cu Ω/kftCu 60°Cu 75°Cu 90°Al Ω/kftAl 60°Al 75°Al 90°
14 AWG0.0641.634,1102.13.14152025————
12 AWG0.0812.056,5303.31.982025303.25152025
10 AWG0.1022.5910,3805.31.243035402.04253035
8 AWG0.1283.2616,5108.40.7784050551.28354045
6 AWG0.1624.1226,24013.30.4915565750.808405055
4 AWG0.2045.1941,74021.10.3087085950.508556575
3 AWG0.2295.8352,62026.70.245851001150.403657585
2 AWG0.2586.5466,36033.60.194951151300.3197590100
1 AWG0.2897.3583,69042.40.1541101301450.25385100115
1/0 AWG0.3258.25105,60053.50.1221251501700.201100120135
2/0 AWG0.3659.27133,10067.40.09671451751950.159115135150
3/0 AWG0.41010.40167,80085.00.07661652002250.126130155175
4/0 AWG0.46011.68211,600107.20.06081952302600.1150180205
250 kcmil0.50012.70250,000126.70.05152152552900.0847170205230
300 kcmil0.54813.91300,000152.00.04292402853200.0707195230260
350 kcmil0.59215.03350,000177.30.03672603103500.0605210250280
400 kcmil0.63216.06400,000202.70.03212803353800.0529225270305
500 kcmil0.70717.96500,000253.40.02583203804300.0424260310350
Copper 14, 12 and 10 AWG are also limited to 15, 20 and 30 A breakers by NEC 240.4(D), whatever the column says.

Wire Size for Common Appliances

NM-B copper, short runs, 240 V unless noted. The appliance’s nameplate or installation manual always wins; for air conditioners and heat pumps, use the nameplate’s minimum circuit ampacity (MCA) and maximum breaker (MOCP) rather than this table.

ApplianceBreakerWire (NM-B Cu)Notes
Electric dryer30 A10 AWG240 V. 10/3 with ground (needs a neutral).
Electric range40 A8 AWGMany ranges call for 40 A; check the nameplate.
Electric range (large)50 A6 AWGUse 8 AWG THHN in conduit with 75 °C terminals.
Wall oven30 A10 AWGCheck the install guide; some double ovens need 40 A.
Water heater, 4,500 W25 A10 AWGContinuous load (× 1.25). Most installers use 30 A with 10 AWG.
Level 2 EV charger, 32 A40 A8 AWGContinuous load. 40 A breaker.
Level 2 EV charger, 48 A60 A4 AWGContinuous. 6 AWG THHN in conduit with 75 °C terminals also works.
Hot tub50 A6 AWGNeeds GFCI protection and a disconnect within sight.
Window AC, 120 V20 A12 AWGSmall units can run on 15 A with 14 AWG.
Well pump, 240 V20 A12 AWGLong runs to the well often need a bigger size: enter the distance.
Garage sub-panel, 60 A60 A4 AWG6 AWG THHN in conduit is the usual choice.

100 and 200 Amp Service Wire Size: the 83% Rule

Service wire for a house is smaller than the same-amp feeder to a sub-panel because a whole home almost never draws its full service rating. NEC 310.12 lets the service-entrance wires, or a main feeder carrying the entire dwelling load, be rated for 83% of the service on a single-phase 120/240 V system from 100 to 400 A. That’s why 200 A service uses 2/0 AWG copper or 4/0 AWG aluminum instead of 3/0 AWG copper.

What changes under the 2026 NEC: the rule now says outright that it applies only to 75 °C-rated wire (the calculator already assumes this), and the load-calculation rules moved from Article 220 to a new Article 120. No state enforces the 2026 edition yet; check which edition your area uses.

Copper or Aluminum Wire?

Aluminum costs much less, which matters on big feeders and services, but it carries less current than copper of the same size, so it usually runs one or two sizes larger. Modern aluminum building wire (AA-8000 alloy) is standard for services and feeders. Use it only with lugs and breakers marked AL or AL/CU, torque connections to the maker’s value, and apply antioxidant compound where the lug maker calls for it. Small aluminum branch circuits are a different story: the solid aluminum wiring in some 1960s–70s homes is a known fire risk, so this calculator offers aluminum only at 8 AWG and larger.

DC Wire Size for Solar, RVs and Boats

Low-voltage DC systems lose a much bigger share of their voltage in the wire: a 0.36 V drop is 3% of 12 V but a rounding error at 240 V. That’s why 12 V runs need thick cable, and why 24 V and 48 V systems use far thinner wire for the same power. The boat standard (ABYC E-11) uses 3% for critical circuits like navigation lights, bilge pumps and electronics, and 10% for things like cabin lighting. Current ratings for fine-strand marine and RV cable depend on its insulation and where it runs, so the calculator’s current check for DC is approximate: confirm with the cable maker’s rating.

Copper size at 12 V for each one-way length (the wire is twice this long, out and back):

Current5 ft10 ft15 ft20 ft30 ft
5 A141412108
10 A1410886
15 A128864
20 A108643
30 A86432
40 A84321/0
50 A64212/0
100 A312/03/0250 kcmil
3% drop at 12 V (critical circuits). Sizes in AWG.
Current5 ft10 ft15 ft20 ft30 ft
5 A1414141414
10 A1414141212
15 A1414121210
20 A121212108
30 A10101086
40 A88866
50 A88864
100 A33332
10% drop at 12 V (non-critical circuits). Sizes in AWG.

Wire Size FAQ

6 AWG copper if you use NM-B (Romex) cable, or 8 AWG copper THHN in conduit when the breaker and the equipment are rated 75 °C. In aluminum (XHHW-2 or SER), 6 AWG. At 240 V a run longer than about 146 ft needs a bigger size to stay under a 3% voltage drop.

Only as individual THHN/THWN-2 wires in conduit, where both ends (breaker and equipment) are rated 75 °C: 8 AWG copper is rated 50 A in that column. In NM-B cable it is limited to the 60 °C column, 40 A, so a 50 A breaker needs 6 AWG.

4 AWG copper or 2 AWG aluminum for the service entrance of a single-family home, using the NEC 83% rule with 75 °C wire. A 100 A feeder to a sub-panel that doesn’t carry the whole house needs 3 AWG copper or 1 AWG aluminum.

3 AWG copper (2.0% drop at the full 100 A) or 1 AWG aluminum (2.1%), at 240 V with 75 °C terminals. Most sub-panels never draw their full rating, so the real drop will be lower.

A 48 A Level 2 charger needs a 60 A breaker (chargers are continuous loads, so 48 × 1.25 = 60 A): 6 AWG copper THHN in conduit, or 4 AWG NM-B. A 32 A charger needs a 40 A breaker and 8 AWG copper. Long runs to a detached garage may need a size up.

Yes. 12 AWG copper is the minimum for a 20 A circuit; 14 AWG is limited to 15 A by NEC 240.4(D). At a full 20 A and 120 V, 12 AWG passes the 3% voltage-drop guideline up to about 46 ft, so longer runs often use 10 AWG.

At 240 V, 8 AWG copper keeps the drop to 1.9% (10 AWG would be about 3.9%). At 120 V you need 6 AWG copper (2.5%). These assume the full 30 A; a lighter load lets you go smaller.

Usually one or two AWG sizes. For a 100 A dwelling service it’s 4 AWG copper or 2 AWG aluminum; for a 200 A service, 2/0 AWG copper or 4/0 AWG aluminum. Aluminum needs connectors rated AL/CU and is best kept to feeders and services.

Method and Sources

Ampacity: NEC 2023 Table 310.16, with the column set by the wire type (NM-B and UF: 60 °C, NEC 334.80 and 340.80) or the terminal rating (110.14(C)); temperature and conductor-count factors from 310.15(B) and (C); small-wire limits from 240.4(D); continuous loads at 125% (210.19(A), 210.20(A)); dwelling services at 83% (310.12); ground wires from Table 250.122 and 250.122(B). Voltage drop: Chapter 9 Table 8 DC resistance at 75 °C, single-phase and DC 2 × I × L × R ÷ 1,000, three-phase √3 × I × L × R ÷ 1,000. Reactance is ignored, which can understate drop by a few percent on AC runs of 1/0 and larger. Out of scope: motors (NEC Article 430), equipment with a nameplate MCA, parallel runs, and codes outside the US.

Written by K. Lynch. See our methodology. Spotted a problem with a result? Tell us (include the result link). Updates: Nov 2026, launched on NEC 2023 tables.