How to Choose the Right Wire Size
Wire size depends on four things: the breaker (or the load), the type of wire and how it’s installed, the material, and the distance. The breaker sets the minimum: the wire must be rated for at least the breaker’s amps, so a fault trips the breaker before the wire overheats. Distance can then push the size up, because long runs lose voltage.
| Breaker | NM-B (Romex) copper | THHN copper in conduit | Aluminum (XHHW-2/SER) | Longest run, 120 V | Longest run, 240 V |
|---|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | — | 39 ft | 78 ft |
| 20 A | 12 AWG | 12 AWG | — | 46 ft | 93 ft |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 49 ft | 99 ft |
| 40 A | 8 AWG | 8 AWG | 8 AWG | 57 ft | 115 ft |
| 50 A | 6 AWG | 8 AWG | 6 AWG | 73 ft | 146 ft |
| 60 A | 4 AWG | 6 AWG | 4 AWG | 97 ft | 194 ft |
| 70 A | 4 AWG | 4 AWG | 3 AWG | 83 ft | 166 ft |
| 80 A | 3 AWG | 4 AWG | 2 AWG | 91 ft | 183 ft |
| 90 A | 2 AWG | 3 AWG | 2 AWG | 103 ft | 206 ft |
| 100 A | — (use SER) | 3 AWG | 1 AWG | 116 ft | 233 ft |
Jump to:15 A20 A30 A40 A50 A60 A100 A service200 A service
What Size Wire for Each Breaker
Each answer below gives the size for a short run, then how it grows with distance at the full breaker rating and a 3% drop. Enter your own distance and load above for an exact answer.
What Size Wire for 15 Amps?
14 AWG copper for a 15 A breaker, in NM-B cable or THHN in conduit. Typical uses: lighting and general-purpose outlets.
| One-way distance | NM-B, 120 V | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|---|
| 50 ft | 12 AWG | 14 AWG | 14 AWG |
| 100 ft | 8 AWG | 12 AWG | 12 AWG |
| 150 ft | 8 AWG | 10 AWG | 10 AWG |
| 200 ft | 6 AWG | 8 AWG | 8 AWG |
| 300 ft | 4 AWG | 8 AWG | 8 AWG |
What Size Wire for 20 Amps?
12 AWG copper for a 20 A breaker, in NM-B cable or THHN in conduit. Typical uses: kitchen, bathroom, laundry and garage outlets; most window air conditioners.
| One-way distance | NM-B, 120 V | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|---|
| 50 ft | 10 AWG | 12 AWG | 12 AWG |
| 100 ft | 8 AWG | 10 AWG | 10 AWG |
| 150 ft | 6 AWG | 8 AWG | 8 AWG |
| 200 ft | 4 AWG | 8 AWG | 8 AWG |
| 300 ft | 3 AWG | 6 AWG | 6 AWG |
What Size Wire for 30 Amps?
10 AWG copper for a 30 A breaker, in NM-B cable or THHN in conduit. Typical uses: electric dryers, smaller water heaters, wall ovens, rv 30 a pedestals (120 v).
| One-way distance | NM-B, 120 V | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|---|
| 50 ft | 8 AWG | 10 AWG | 10 AWG |
| 100 ft | 6 AWG | 8 AWG | 8 AWG |
| 150 ft | 4 AWG | 8 AWG | 8 AWG |
| 200 ft | 3 AWG | 6 AWG | 6 AWG |
| 300 ft | 2 AWG | 4 AWG | 4 AWG |
What Size Wire for 40 Amps?
8 AWG copper for a 40 A breaker, in NM-B cable or THHN in conduit. Typical uses: electric ranges and cooktops, 32 a ev chargers.
| One-way distance | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|
| 50 ft | 8 AWG | 8 AWG |
| 100 ft | 8 AWG | 8 AWG |
| 150 ft | 6 AWG | 6 AWG |
| 200 ft | 4 AWG | 4 AWG |
| 300 ft | 3 AWG | 3 AWG |
What Size Wire for 50 Amps?
6 AWG copper in NM-B cable (rated 55 A in the 60 °C column), or 8 AWG copper THHN in conduit with 75 °C terminals (50 A). Typical uses: large ranges, hot tubs, rv 50 a pedestals, welders.
Is 8 gauge OK on a 50 amp breaker? Yes for THHN/THWN-2 wires in conduit when the breaker and the equipment are both rated 75 °C; no for NM-B, where 8 AWG is limited to 40 A. That’s why forum answers disagree: both sides are right for different wire.
| One-way distance | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|
| 50 ft | 6 AWG | 8 AWG |
| 100 ft | 6 AWG | 6 AWG |
| 150 ft | 4 AWG | 4 AWG |
| 200 ft | 4 AWG | 4 AWG |
| 300 ft | 2 AWG | 2 AWG |
What Size Wire for 60 Amps?
4 AWG copper in NM-B cable (rated 70 A in the 60 °C column), or 6 AWG copper THHN in conduit with 75 °C terminals (65 A). Typical uses: 48 a ev chargers, small sub-panels, tankless water heaters.
Strictly, NM-B on a 60 A breaker needs 4 AWG. 6 AWG NM-B is rated 55 A, and NEC 240.4(B) may allow it on a 60 A breaker for a single appliance. Ask your electrician; the calculator doesn’t apply it.
| One-way distance | NM-B, 240 V | THHN in conduit, 240 V |
|---|---|---|
| 50 ft | 4 AWG | 6 AWG |
| 100 ft | 4 AWG | 6 AWG |
| 150 ft | 4 AWG | 4 AWG |
| 200 ft | 3 AWG | 3 AWG |
| 300 ft | 2 AWG | 2 AWG |
What Size Wire for 100 Amp Service?
4 AWG copper or 2 AWG aluminum for a 100 A single-family service entrance. The NEC lets these wires carry 83% of the rating (83 A), and 4 AWG copper is rated 85 A, 2 AWG aluminum 90 A, at 75 °C.
A 100 A feeder to a sub-panel that doesn’t carry the whole house can’t use the 83% rule: it needs 3 AWG copper or 1 AWG aluminum, and more over long distances:
| One-way distance | Copper THHN, 240 V | Aluminum SER, 240 V |
|---|---|---|
| 50 ft | 3 AWG | 1 AWG |
| 100 ft | 3 AWG | 1 AWG |
| 150 ft | 2 AWG | 1/0 AWG |
| 200 ft | 1 AWG | 2/0 AWG |
| 300 ft | 2/0 AWG | 4/0 AWG |
What Size Wire for 200 Amp Service?
2/0 AWG copper or 4/0 AWG aluminum for a 200 A single-family service entrance. The NEC lets these wires carry 83% of the rating (166 A), and 2/0 AWG copper is rated 175 A, 4/0 AWG aluminum 180 A, at 75 °C.
A 200 A feeder to a sub-panel that doesn’t carry the whole house can’t use the 83% rule: it needs 3/0 AWG copper or 250 kcmil aluminum, and more over long distances:
| One-way distance | Copper THHN, 240 V | Aluminum SER, 240 V |
|---|---|---|
| 50 ft | 3/0 AWG | 250 kcmil |
| 100 ft | 3/0 AWG | 250 kcmil |
| 150 ft | 3/0 AWG | 250 kcmil |
| 200 ft | 3/0 AWG | 250 kcmil |
| 300 ft | 250 kcmil | 400 kcmil |
Why the Same Breaker Can Need Two Different Wire Sizes
Every wire size has three current ratings in NEC Table 310.16, one for each insulation temperature: 60, 75 and 90 °C. Which one you may use depends on the weakest link. NM-B cable (Romex) is always held to the 60 °C rating (NEC 334.80), even though the wires inside are rated 90 °C. Individual wires in conduit can use the 75 °C rating, but only if the breaker and the equipment at the other end are marked 75 °C (NEC 110.14(C)). The 90 °C rating is only a starting point when you have to derate for heat or crowded conduit.
The calculator asks for the wire type for this reason, and shows which rule decided the size under every answer.
Long Runs: When Distance Decides the Wire Size
A wire can be big enough not to overheat and still too small for its length. Every foot adds resistance, and the voltage lost in the wire is voltage your equipment doesn’t get. The NEC recommends keeping that drop under 3% on a branch circuit and 5% in total (an informational note, not a rule), and it’s a sensible target for motors, chargers and anything with electronics.
Example: a 50 A RV pedestal 300 ft from the house. 8 AWG copper carries 50 A, but over that distance it would lose far more than 3%. The calculator steps up one size at a time and lands on 2 AWG copper (2.4%) or 1/0 AWG aluminum (2.5%). The size ladder under the result shows the size below failing and the size above passing more easily.
Upsized the wire? Upsize the ground too. When wire is made bigger for voltage drop, NEC 250.122(B) requires the ground wire to grow by the same proportion. The calculator does this for you; many guides forget it.
AWG Wire Size Chart
Diameter is for the bare conductor (solid equivalent). Ampacity is NEC 2023 Table 310.16 at 30 °C (86 °F) with no more than three current-carrying wires together; resistance is Chapter 9 Table 8 at 75 °C, in ohms per 1,000 ft.
| Size | Dia. (in) | Dia. (mm) | Area (cmil) | Area (mm²) | Cu Ω/kft | Cu 60° | Cu 75° | Cu 90° | Al Ω/kft | Al 60° | Al 75° | Al 90° |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 0.064 | 1.63 | 4,110 | 2.1 | 3.14 | 15 | 20 | 25 | — | — | — | — |
| 12 AWG | 0.081 | 2.05 | 6,530 | 3.3 | 1.98 | 20 | 25 | 30 | 3.25 | 15 | 20 | 25 |
| 10 AWG | 0.102 | 2.59 | 10,380 | 5.3 | 1.24 | 30 | 35 | 40 | 2.04 | 25 | 30 | 35 |
| 8 AWG | 0.128 | 3.26 | 16,510 | 8.4 | 0.778 | 40 | 50 | 55 | 1.28 | 35 | 40 | 45 |
| 6 AWG | 0.162 | 4.12 | 26,240 | 13.3 | 0.491 | 55 | 65 | 75 | 0.808 | 40 | 50 | 55 |
| 4 AWG | 0.204 | 5.19 | 41,740 | 21.1 | 0.308 | 70 | 85 | 95 | 0.508 | 55 | 65 | 75 |
| 3 AWG | 0.229 | 5.83 | 52,620 | 26.7 | 0.245 | 85 | 100 | 115 | 0.403 | 65 | 75 | 85 |
| 2 AWG | 0.258 | 6.54 | 66,360 | 33.6 | 0.194 | 95 | 115 | 130 | 0.319 | 75 | 90 | 100 |
| 1 AWG | 0.289 | 7.35 | 83,690 | 42.4 | 0.154 | 110 | 130 | 145 | 0.253 | 85 | 100 | 115 |
| 1/0 AWG | 0.325 | 8.25 | 105,600 | 53.5 | 0.122 | 125 | 150 | 170 | 0.201 | 100 | 120 | 135 |
| 2/0 AWG | 0.365 | 9.27 | 133,100 | 67.4 | 0.0967 | 145 | 175 | 195 | 0.159 | 115 | 135 | 150 |
| 3/0 AWG | 0.410 | 10.40 | 167,800 | 85.0 | 0.0766 | 165 | 200 | 225 | 0.126 | 130 | 155 | 175 |
| 4/0 AWG | 0.460 | 11.68 | 211,600 | 107.2 | 0.0608 | 195 | 230 | 260 | 0.1 | 150 | 180 | 205 |
| 250 kcmil | 0.500 | 12.70 | 250,000 | 126.7 | 0.0515 | 215 | 255 | 290 | 0.0847 | 170 | 205 | 230 |
| 300 kcmil | 0.548 | 13.91 | 300,000 | 152.0 | 0.0429 | 240 | 285 | 320 | 0.0707 | 195 | 230 | 260 |
| 350 kcmil | 0.592 | 15.03 | 350,000 | 177.3 | 0.0367 | 260 | 310 | 350 | 0.0605 | 210 | 250 | 280 |
| 400 kcmil | 0.632 | 16.06 | 400,000 | 202.7 | 0.0321 | 280 | 335 | 380 | 0.0529 | 225 | 270 | 305 |
| 500 kcmil | 0.707 | 17.96 | 500,000 | 253.4 | 0.0258 | 320 | 380 | 430 | 0.0424 | 260 | 310 | 350 |
Wire Size for Common Appliances
NM-B copper, short runs, 240 V unless noted. The appliance’s nameplate or installation manual always wins; for air conditioners and heat pumps, use the nameplate’s minimum circuit ampacity (MCA) and maximum breaker (MOCP) rather than this table.
| Appliance | Breaker | Wire (NM-B Cu) | Notes |
|---|---|---|---|
| Electric dryer | 30 A | 10 AWG | 240 V. 10/3 with ground (needs a neutral). |
| Electric range | 40 A | 8 AWG | Many ranges call for 40 A; check the nameplate. |
| Electric range (large) | 50 A | 6 AWG | Use 8 AWG THHN in conduit with 75 °C terminals. |
| Wall oven | 30 A | 10 AWG | Check the install guide; some double ovens need 40 A. |
| Water heater, 4,500 W | 25 A | 10 AWG | Continuous load (× 1.25). Most installers use 30 A with 10 AWG. |
| Level 2 EV charger, 32 A | 40 A | 8 AWG | Continuous load. 40 A breaker. |
| Level 2 EV charger, 48 A | 60 A | 4 AWG | Continuous. 6 AWG THHN in conduit with 75 °C terminals also works. |
| Hot tub | 50 A | 6 AWG | Needs GFCI protection and a disconnect within sight. |
| Window AC, 120 V | 20 A | 12 AWG | Small units can run on 15 A with 14 AWG. |
| Well pump, 240 V | 20 A | 12 AWG | Long runs to the well often need a bigger size: enter the distance. |
| Garage sub-panel, 60 A | 60 A | 4 AWG | 6 AWG THHN in conduit is the usual choice. |
100 and 200 Amp Service Wire Size: the 83% Rule
Service wire for a house is smaller than the same-amp feeder to a sub-panel because a whole home almost never draws its full service rating. NEC 310.12 lets the service-entrance wires, or a main feeder carrying the entire dwelling load, be rated for 83% of the service on a single-phase 120/240 V system from 100 to 400 A. That’s why 200 A service uses 2/0 AWG copper or 4/0 AWG aluminum instead of 3/0 AWG copper.
What changes under the 2026 NEC: the rule now says outright that it applies only to 75 °C-rated wire (the calculator already assumes this), and the load-calculation rules moved from Article 220 to a new Article 120. No state enforces the 2026 edition yet; check which edition your area uses.
Copper or Aluminum Wire?
Aluminum costs much less, which matters on big feeders and services, but it carries less current than copper of the same size, so it usually runs one or two sizes larger. Modern aluminum building wire (AA-8000 alloy) is standard for services and feeders. Use it only with lugs and breakers marked AL or AL/CU, torque connections to the maker’s value, and apply antioxidant compound where the lug maker calls for it. Small aluminum branch circuits are a different story: the solid aluminum wiring in some 1960s–70s homes is a known fire risk, so this calculator offers aluminum only at 8 AWG and larger.
DC Wire Size for Solar, RVs and Boats
Low-voltage DC systems lose a much bigger share of their voltage in the wire: a 0.36 V drop is 3% of 12 V but a rounding error at 240 V. That’s why 12 V runs need thick cable, and why 24 V and 48 V systems use far thinner wire for the same power. The boat standard (ABYC E-11) uses 3% for critical circuits like navigation lights, bilge pumps and electronics, and 10% for things like cabin lighting. Current ratings for fine-strand marine and RV cable depend on its insulation and where it runs, so the calculator’s current check for DC is approximate: confirm with the cable maker’s rating.
Copper size at 12 V for each one-way length (the wire is twice this long, out and back):
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 30 ft |
|---|---|---|---|---|---|
| 5 A | 14 | 14 | 12 | 10 | 8 |
| 10 A | 14 | 10 | 8 | 8 | 6 |
| 15 A | 12 | 8 | 8 | 6 | 4 |
| 20 A | 10 | 8 | 6 | 4 | 3 |
| 30 A | 8 | 6 | 4 | 3 | 2 |
| 40 A | 8 | 4 | 3 | 2 | 1/0 |
| 50 A | 6 | 4 | 2 | 1 | 2/0 |
| 100 A | 3 | 1 | 2/0 | 3/0 | 250 kcmil |
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 30 ft |
|---|---|---|---|---|---|
| 5 A | 14 | 14 | 14 | 14 | 14 |
| 10 A | 14 | 14 | 14 | 12 | 12 |
| 15 A | 14 | 14 | 12 | 12 | 10 |
| 20 A | 12 | 12 | 12 | 10 | 8 |
| 30 A | 10 | 10 | 10 | 8 | 6 |
| 40 A | 8 | 8 | 8 | 6 | 6 |
| 50 A | 8 | 8 | 8 | 6 | 4 |
| 100 A | 3 | 3 | 3 | 3 | 2 |
Wire Size FAQ
Method and Sources
Ampacity: NEC 2023 Table 310.16, with the column set by the wire type (NM-B and UF: 60 °C, NEC 334.80 and 340.80) or the terminal rating (110.14(C)); temperature and conductor-count factors from 310.15(B) and (C); small-wire limits from 240.4(D); continuous loads at 125% (210.19(A), 210.20(A)); dwelling services at 83% (310.12); ground wires from Table 250.122 and 250.122(B). Voltage drop: Chapter 9 Table 8 DC resistance at 75 °C, single-phase and DC 2 × I × L × R ÷ 1,000, three-phase √3 × I × L × R ÷ 1,000. Reactance is ignored, which can understate drop by a few percent on AC runs of 1/0 and larger. Out of scope: motors (NEC Article 430), equipment with a nameplate MCA, parallel runs, and codes outside the US.