How to Calculate Voltage Drop
Voltage drop is the voltage lost in the wire between the panel and the load. It depends on the current, the length, and the wire’s resistance, which falls as the wire gets thicker.
Single-phase and DC: VD = 2 × I × L × R ÷ 1,000
Three-phase: VD = 1.732 × I × L × R ÷ 1,000
Percent drop = VD ÷ system voltage × 100
I is the current in amps, L the one-way length in feet, and R the wire’s resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8. The 2 counts both wires, out and back.
Worked examples
- 120 V, 20 A, 100 ft of 12 AWG copper (solid, 1.93 Ω/kft): 2 × 20 × 100 × 1.93 ÷ 1,000 = 7.72 V, or 6.4% of 120 V. Over the 3% guideline; 8 AWG brings it to 2.6%.
- 240 V sub-panel, 50 A, 150 ft of 6 AWG copper (0.491 Ω/kft): 2 × 50 × 150 × 0.491 ÷ 1,000 = 7.37 V, 3.07%. Just over 3%, within 5%; 4 AWG gives 1.9%.
- Three-phase 208 V, 50 A, 100 ft of 6 AWG copper: 1.732 × 50 × 100 × 0.491 ÷ 1,000 = 4.25 V, 2.0%.
- 12 V DC, 20 A, 15 ft of 10 AWG copper (1.24 Ω/kft): 2 × 20 × 15 × 1.24 ÷ 1,000 = 0.744 V, which is 6.2% of 12 V.
Quick hand-check: the K-constant formula, VD = 2 × K × I × L ÷ circular mils with K = 12.9 for copper and 21.2 for aluminum, gives 7.90 V for example 1. It’s within a few percent of the Table 8 method.
How Far Can You Run Each Wire Size?
Longest one-way run in feet before copper passes a 3% drop. Full load uses the circuit’s rated current; 80% is a more typical running load.
| Copper | Circuit | 120 V, full | 120 V, 80% | 240 V, full | 240 V, 80% |
|---|---|---|---|---|---|
| 14 AWG | 15 A | 38 | 47 | 76 | 95 |
| 12 AWG | 20 A | 45 | 56 | 90 | 113 |
| 10 AWG | 30 A | 48 | 60 | 96 | 120 |
| 8 AWG | 50 A | 46 | 57 | 92 | 115 |
| 6 AWG | 60 A | 61 | 76 | 122 | 152 |
| 4 AWG | 80 A | 73 | 91 | 146 | 182 |
| 3 AWG | 100 A | 73 | 91 | 146 | 183 |
| 2 AWG | 110 A | 84 | 105 | 168 | 210 |
| 1 AWG | 125 A | 93 | 116 | 187 | 233 |
| 1/0 AWG | 150 A | 98 | 122 | 196 | 245 |
| 2/0 AWG | 175 A | 106 | 132 | 212 | 265 |
What Is an Acceptable Voltage Drop?
- 3% on a branch circuit, 5% in total (feeder plus branch). These are NEC informational notes after 210.19 and 215.2: recommendations for reasonable efficiency, not enforceable rules.
- 1.5% branch, 2.5% total for sensitive electronic equipment under NEC Article 647. This one is a requirement where the article applies.
- Boats: 3% for critical circuits (navigation lights, bilge pumps, electronics, panel feeders) and 10% for non-critical ones, under the ABYC E-11 standard. RV and off-grid solar installers commonly follow the same split.
What too much drop does: motors run hotter and may struggle to start, heaters lose output (heat falls with the square of the voltage), EV chargers may slow down or fault, and LED drivers and electronics can flicker or reset.
How to Reduce Voltage Drop
Using example 1 (20 A, 100 ft, 12 AWG, 6.4%):
- Bigger wire: 8 AWG brings it to 2.6%.
- Higher voltage: the same 2,400 W at 240 V draws 10 A, so the drop falls to 1.6%.
- Shorter route: 12 AWG passes 3% up to about 47 ft.
- A sub-panel near the loads: one large feeder with low drop, then short branch circuits.
- Parallel runs or less load per circuit: two sets of wire halve the drop; splitting the load across two circuits does the same.
What Voltage Drop Costs You
The lost voltage becomes heat in the wire, and you pay for it. On long, heavily used circuits, one wire size up can pay for itself.
| Circuit | Use | Smaller wire | One size up | Saved a year |
|---|---|---|---|---|
| Level 2 EV charger | 32 A, 100 ft, 3 h/day | 8 AWG: 2.1%, 159 W, $30/yr | 6 AWG: 1.3%, 101 W, $19/yr | $11 |
| Shop heater, 240 V | 24 A, 150 ft, 6 h/day | 10 AWG: 3.7%, 214 W, $80/yr | 8 AWG: 2.3%, 134 W, $50/yr | $30 |
| Well pump | 10 A, 300 ft, 2 h/day | 12 AWG: 5.0%, 119 W, $15/yr | 10 AWG: 3.1%, 74 W, $9/yr | $6 |
Why Voltage Drop Calculators Disagree
Different tools give slightly different answers for the same run. Three things explain it: the resistance they use (NEC Table 8 at 75 °C, which this calculator uses, or a K constant), the conductor temperature they assume (resistance is lower when the wire is cool, so 75 °C values are conservative), and whether they include AC reactance from NEC Chapter 9 Table 9. Reactance matters mostly on AC runs of 1/0 and larger in steel conduit, where it can add a few percent. For homes and small buildings, the differences are too small to change the wire size.
Voltage Drop FAQ
Method and Sources
Resistance: NEC 2023 Chapter 9 Table 8, uncoated copper and aluminum at 75 °C (solid values for copper 14–10 AWG when selected). Formulas as above; current from watts uses I = W ÷ (V × PF) for single-phase, W ÷ (1.732 × V × PF) for three-phase and W ÷ V for DC. Power lost: 2 × I² × R for single-phase and DC, 3 × I² × R for three-phase. Ampacity check: Table 310.16 at 75 °C.
- NFPA 70, National Electrical Code (free read-only access)
- EEPower: computing voltage drop in branch circuits and feeders
- EC&M: Watch out for that voltage drop
- ABYC: What is voltage drop (E-11)
Written by K. Lynch. See our methodology. Spotted a problem with a result? Tell us (include the result link). Updates: Nov 2026, launched on NEC 2023 tables.