Voltage Drop Calculator

Voltage drop is the voltage lost in the wire. For single-phase circuits, VD = 2 × I × L × R ÷ 1,000. Keep it under 3% on a branch circuit and 5% in total. Example: 20 A over 100 ft of 12 AWG copper loses 7.7 V.

Voltage drop calculator

Material
Panel to load, along the wire’s route. Not the round trip.
Load
Use the real running load, not the breaker size, for a realistic drop.
Advanced: parallel runs, power factor, cost of the loss
Enter the length and the load to see the voltage drop.

How to Calculate Voltage Drop

Voltage drop is the voltage lost in the wire between the panel and the load. It depends on the current, the length, and the wire’s resistance, which falls as the wire gets thicker.

Single-phase and DC: VD = 2 × I × L × R ÷ 1,000
Three-phase: VD = 1.732 × I × L × R ÷ 1,000
Percent drop = VD ÷ system voltage × 100

I is the current in amps, L the one-way length in feet, and R the wire’s resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8. The 2 counts both wires, out and back.

One-way length versus round tripA panel on the left feeds a load on the right 100 feet away. Current flows out on the hot wire and back on the neutral, so the wire is 200 feet of round trip. Calculators ask for the one-way length and double it. Panel Load hot: current out →← neutral: current back one-way length L = 100 ft (enter this) · wire carrying current = 2 × L The drop happens on both wires, which is where the “2” in the formula comes from
Measure the one-way length. The formula doubles it.

Worked examples

  1. 120 V, 20 A, 100 ft of 12 AWG copper (solid, 1.93 Ω/kft): 2 × 20 × 100 × 1.93 ÷ 1,000 = 7.72 V, or 6.4% of 120 V. Over the 3% guideline; 8 AWG brings it to 2.6%.
  2. 240 V sub-panel, 50 A, 150 ft of 6 AWG copper (0.491 Ω/kft): 2 × 50 × 150 × 0.491 ÷ 1,000 = 7.37 V, 3.07%. Just over 3%, within 5%; 4 AWG gives 1.9%.
  3. Three-phase 208 V, 50 A, 100 ft of 6 AWG copper: 1.732 × 50 × 100 × 0.491 ÷ 1,000 = 4.25 V, 2.0%.
  4. 12 V DC, 20 A, 15 ft of 10 AWG copper (1.24 Ω/kft): 2 × 20 × 15 × 1.24 ÷ 1,000 = 0.744 V, which is 6.2% of 12 V.

Quick hand-check: the K-constant formula, VD = 2 × K × I × L ÷ circular mils with K = 12.9 for copper and 21.2 for aluminum, gives 7.90 V for example 1. It’s within a few percent of the Table 8 method.

How Far Can You Run Each Wire Size?

Longest one-way run in feet before copper passes a 3% drop. Full load uses the circuit’s rated current; 80% is a more typical running load.

CopperCircuit120 V, full120 V, 80%240 V, full240 V, 80%
14 AWG15 A38477695
12 AWG20 A455690113
10 AWG30 A486096120
8 AWG50 A465792115
6 AWG60 A6176122152
4 AWG80 A7391146182
3 AWG100 A7391146183
2 AWG110 A84105168210
1 AWG125 A93116187233
1/0 AWG150 A98122196245
2/0 AWG175 A106132212265
Stranded copper, Table 8 at 75 °C. Circuit current is the 240.4(D) limit for 14–10 AWG and the largest standard breaker within the 75 °C rating above that.
Voltage drop by distance, 20 amps at 120 voltsPercent drop rises in a straight line with distance. At 20 amps and 120 volts, 12 AWG copper reaches the 3 percent guideline at about 47 feet, 10 AWG at about 74 feet and 8 AWG at about 116 feet.0%2%4%6%8%10%0 ft50 ft100 ft150 ft200 ft3% guideline12 AWG: 47 ft10 AWG: 74 ft8 AWG: 116 ft
At 20 A and 120 V, each size up buys roughly half again as much distance before the 3% line.

What Is an Acceptable Voltage Drop?

What too much drop does: motors run hotter and may struggle to start, heaters lose output (heat falls with the square of the voltage), EV chargers may slow down or fault, and LED drivers and electronics can flicker or reset.

How to Reduce Voltage Drop

Using example 1 (20 A, 100 ft, 12 AWG, 6.4%):

What Voltage Drop Costs You

The lost voltage becomes heat in the wire, and you pay for it. On long, heavily used circuits, one wire size up can pay for itself.

CircuitUseSmaller wireOne size upSaved a year
Level 2 EV charger32 A, 100 ft, 3 h/day8 AWG: 2.1%, 159 W, $30/yr6 AWG: 1.3%, 101 W, $19/yr$11
Shop heater, 240 V24 A, 150 ft, 6 h/day10 AWG: 3.7%, 214 W, $80/yr8 AWG: 2.3%, 134 W, $50/yr$30
Well pump10 A, 300 ft, 2 h/day12 AWG: 5.0%, 119 W, $15/yr10 AWG: 3.1%, 74 W, $9/yr$6
240 V copper at $0.17/kWh. Enter your own hours and rate in the calculator’s Advanced options.

Why Voltage Drop Calculators Disagree

Different tools give slightly different answers for the same run. Three things explain it: the resistance they use (NEC Table 8 at 75 °C, which this calculator uses, or a K constant), the conductor temperature they assume (resistance is lower when the wire is cool, so 75 °C values are conservative), and whether they include AC reactance from NEC Chapter 9 Table 9. Reactance matters mostly on AC runs of 1/0 and larger in steel conduit, where it can add a few percent. For homes and small buildings, the differences are too small to change the wire size.

Voltage Drop FAQ

For single-phase AC and DC: voltage drop = 2 × amps × one-way length (ft) × resistance (ohms per 1,000 ft) ÷ 1,000. For three-phase, use 1.732 instead of 2. Example: 20 A over 100 ft of 12 AWG copper (1.93 Ω/kft) loses 7.72 V, which is 6.4% of 120 V.

The NEC recommends sizing branch circuits for no more than 3% voltage drop at the farthest outlet, and no more than 5% for the feeder and branch circuit together. It appears in informational notes, so it is guidance, not an enforceable rule.

Generally no. The 3% and 5% figures are informational notes. A few specific cases are mandatory, such as circuits for sensitive electronic equipment under Article 647 (1.5% branch, 2.5% total) and fire pump circuits. Some local codes and energy codes also set limits.

About 45 ft at 120 V before a full 20 A load passes 3% drop, or 56 ft at a 16 A (80%) load. At 240 V the distances double: 90 ft at 20 A. Past that, use 10 AWG.

Yes. The lost voltage turns into heat in the wire. A 32 A EV charger 100 ft away on 8 AWG copper wastes about 159 W while charging, roughly $30 a year at 3 hours a day and $0.17/kWh. One size up cuts that by about a third.

Single-phase and DC circuits count the wire twice (out and back), so the formula multiplies by 2. Balanced three-phase circuits multiply by √3 (1.732), because the return current is shared between the phases. The same wire and current drop about 13% fewer volts on three-phase.

Because the same volts lost are a much bigger share. 0.74 V is 6.2% of 12 V but 0.6% of 120 V. Low-voltage systems also carry more current for the same power. Doubling to 24 V halves the current and cuts the percentage drop to a quarter.

Method and Sources

Resistance: NEC 2023 Chapter 9 Table 8, uncoated copper and aluminum at 75 °C (solid values for copper 14–10 AWG when selected). Formulas as above; current from watts uses I = W ÷ (V × PF) for single-phase, W ÷ (1.732 × V × PF) for three-phase and W ÷ V for DC. Power lost: 2 × I² × R for single-phase and DC, 3 × I² × R for three-phase. Ampacity check: Table 310.16 at 75 °C.

Written by K. Lynch. See our methodology. Spotted a problem with a result? Tell us (include the result link). Updates: Nov 2026, launched on NEC 2023 tables.