Conduit Fill Calculator

Three #6 THHN and a #10 ground, a typical 60 A garage feed, fill 3/4 in. Schedule 40 PVC to 34%, under the 40% limit. In Schedule 80 the same wires reach 42% and need 1 in. Enter your wires below for the fill, the smallest pipe that fits and how many of one wire it takes.

Conduit fill calculator

Wires in the pipe

Count every wire, grounds included. A 120 V circuit’s neutral carries current; a neutral shared by two hots on 120/240 V doesn’t.

Cables by outside diameter: Cat6, coax, Romex

Enter the outside diameter from the spec sheet. Cat6 is usually 0.21 to 0.27 in. (5.4 to 6.9 mm). For a flat cable such as Romex, use the wide side. Each cable counts as one conductor.

Add the wires that go in the pipe.

How a Fill Check Works

Three numbers decide it. NEC Chapter 9 Table 4 gives the inside area of the pipe, Table 5 gives the area of each wire with its insulation, and Table 1 sets how much of the pipe the wires may take: 53% for one wire, 31% for two and 40% for three or more. Add up the wire areas, divide by the pipe area, and compare.

The default above is a 60 A feed to a detached garage: two #6 THHN hots, a #6 neutral and a #10 ground. That is 3 × 0.0507 + 0.0211 = 0.1732 sq in. A 3/4 in. Schedule 40 PVC has 0.508 sq in inside, so the wires fill 34.1% of it, under the 40% limit of 0.2032 sq in. The limit exists so the wires can be pulled in without scraping their insulation and can shed heat once they carry current.

Same Trade Size, Different Pipe

“3/4 in.” is a trade name, not a measurement. Each type has its own wall thickness, so the inside area changes a lot at the same size. Switch the garage feed to Schedule 80 PVC and the same four wires fill 42.3% of it, which fails; it needs 1 in. Schedule 80 (25.2% full). Size the whole run for its tightest piece. If Schedule 80 is used where the pipe comes out of the ground, that section sets the size.

3/4 in. pipeInside area (sq in)40% allowedHolds the garage feed?
IMC (intermediate metal conduit)0.5860.234Yes
Rigid metal conduit (RMC, GRC)0.5490.220Yes
Liquidtight flexible metal (LFMC)0.5410.216Yes
EMT (thin-wall steel tubing)0.5330.213Yes
Flexible metal conduit (FMC, Greenfield)0.5330.213Yes
PVC Schedule 400.5080.203Yes
ENT (flexible nonmetallic tubing)0.5080.203Yes
PVC Schedule 800.4090.164No

Inside areas from NEC Chapter 9 Table 4. The garage feed needs 0.1732 sq in.

Why Two Wires Get the Lowest Limit

One wire may take 53% and three or more 40%, but two only 31%. The usual explanation is that two round wires side by side reach almost across a small pipe and can wedge against the wall in a bend. So two #1 THHN in 1 in. EMT fail at 36.2% full, a number that looks safely under 40%. It mostly turns up in metal conduit, where the pipe itself can serve as the ground, so a 240 V circuit is just two wires.

The 0.8 Rule, and Why Annex C Disagrees With Your Math

A question that comes up on electricians’ forums again and again: Annex C says three #2 THHN fit in 1 in. EMT, but three × 0.1158 = 0.3474 sq in, which is over the 0.3456 the pipe allows. Both are right. Note 7 to Table 1 says that when every conductor is the same size, a count with a decimal of 0.8 or more rounds up. Here 0.3456 ÷ 0.1158 = 2.98, so three are allowed, and Annex C is built that way. Annex C itself is informational; the Chapter 9 rule is what you’re held to.

The rounding only works for one wire size. Add a #14 ground to those three #2 and the sizes are mixed, the area rule applies as written, and you need 1-1/4 in. The calculator says when the 0.8 rule is what let a pipe pass, so you know there is no slack left.

Grounds, Bare Wire and Cables

The equipment ground counts, insulated or bare. People leave it out more than anything else, and in a tight pipe it is often the wire that tips it over. A bare ground uses Table 8 instead of Table 5: bare #10 is 0.011 sq in against 0.0211 for #10 THHN, about half the space.

Cables are entered by outside diameter, and each counts as one conductor. A flat cable such as Romex counts as a circle the size of its wide side, which wastes space and is why a single NM cable in a sleeve uses the 53% limit. Data cable varies more than people expect: Southwire’s Cat6 is 0.213 in. across and Prysmian’s GenSPEED 6000 is 0.240 in., so 1 in. EMT holds 9 of one or 7 of the other.

Fill Is Not Derating

A pipe can pass fill and still need bigger wire. When more than three current-carrying wires share a raceway longer than 24 in., Table 310.15(C)(1) cuts each wire’s ampacity: 80% for 4 to 6, 70% for 7 to 9, 50% for 10 to 20, and lower past that. Grounds never count. A neutral that only carries the imbalance between two hots, as on a 120/240 V feeder, doesn’t count either; the neutral of a plain 120 V circuit does.

Two 20 A circuits sharing a pipe give four current-carrying #12 THHN. Their 90 °C rating of 30 A × 0.8 = 24 A, still above the 20 A breaker, which is why a couple of circuits together rarely force a bigger wire. Put ten in one pipe and 30 × 0.5 = 15 A, and they do. The result shows a note when your wires pass three; our wire size calculator handles the ampacity itself.

What the Fill Limit Doesn’t Cover

Passing 40% doesn’t promise an easy pull. Three wires of one size can jam in a bend when the pipe’s inside diameter is 2.8 to 3.2 times the wire’s, because they line up flat across it. Three #2 THHN in 1 in. EMT come out at 2.73, just below that range; the full plan shows the ratio whenever you enter three of a kind. The code also limits a run to 360° of bends between pull points, and long runs with three or four elbows pull far easier one size up.

Leave room for what comes later, too. A pipe sized to the limit today means a new pipe for the next circuit. Fill in boxes and conduit bodies is a separate count under 314.16, and voltage drop on a long feed is checked with our voltage drop calculator.

Check before you wire. Based on the 2023 National Electrical Code. Your city or state may use a different edition or local amendments, and electrical work usually needs a permit. Have a licensed electrician do the work or check it.

Conduit Fill Questions

9 THHN. 40% of 1/2 in. EMT is 0.1216 sq in and each #12 THHN takes 0.0133, which works out to 9.14. Use #14 and the answer is 12. Schedule 40 PVC at the same trade size holds only 8 #12, because its wall is thicker.

16 #12 THHN, 22 #14 or 10 #10. The #14 count is 21.98 by area, which the 0.8 rule rounds up to 22. For #8 THHN it is 6, again only after rounding 5.82 up.

With copper, two #3 THHN hots, a #3 neutral and a #8 ground add up to 0.3285 sq in. That fits 1 in. EMT at 38% and 1 in. Schedule 40 PVC at 39.5%, but Schedule 80 needs 1-1/4 in. Aluminum feeders are bigger, so check them separately.

Yes, a nipple of 24 in. or less may be filled to 60% instead of 40%, and its wires don’t need ampacity derating. A 1/2 in. EMT nipple takes 13 #12 THHN, against 9 in a longer run. Tick the nipple box above to check one.

It depends on the cable. Southwire’s Cat6 CMR is 0.213 in. across and Prysmian’s GenSPEED 6000 is 0.240 in. In 1 in. EMT at 40% that is 9 or 7 cables; in 3/4 in., 5 or 4. Data installers often stop well short of 40% so cables can be added later.

Any fill calculator built on NEC Chapter 9 should agree when you pick the same wire type, pipe and size. Answers usually differ because of the wire type (#6 XHHW is 0.059 sq in against 0.0507 for THHN), Schedule 40 versus 80, or whether the 0.8 rule was applied.

Yes. Table 5 lists THHN, THWN and THWN-2 on the same row, and most wire sold today carries all three ratings. THW is the one that runs bigger: #12 THW is 0.0181 sq in against 0.0133 for THHN, about 36% more.

Raceway areas come from NEC Chapter 9 Table 4 as published by PDH Online, Conduit.site and EngineerCalcs, and the wire areas from Tables 5 and 8; where sources disagreed on a cell we left the type out rather than guess. We test the engine on the worked examples above, on Annex C counts for THHN in EMT, and on more than 220,000 combinations of pipe, size, wire and count.

Written and checked by Kris Lynch. Not reviewed by a licensed electrician. See our methodology. Spotted a problem? Tell us. Updates: Nov 2026, launched.