One Unit, Two Loads
An air conditioner is sized for summer and a furnace for winter. A heat pump does both jobs with one compressor, so it has one size and two loads to meet. The default house above, 2,000 sq ft with average insulation in zone 5, gains 40,000 BTU/h on a hot day and loses 49,000 BTU/h on a 0 °F night. Size it for summer and it is short in winter; size it for winter and it is oversized all summer.
Which load is bigger depends on where you live. With the same house, summer wins in zones 1 to 4 and winter wins from zone 5 north:
| Zone | Example cities | Design day | Heat gain (BTU/h) | Heat loss (BTU/h) | Bigger load |
|---|---|---|---|---|---|
| Zone 1 | Miami, Honolulu | 45 °F | 60,000 | 17,500 | Cooling |
| Zone 2 | Houston, Phoenix, Orlando | 30 °F | 54,000 | 28,000 | Cooling |
| Zone 3 | Atlanta, Dallas, Los Angeles | 22 °F | 50,000 | 33,600 | Cooling |
| Zone 4 | Washington DC, St. Louis, Seattle | 12 °F | 44,000 | 40,600 | Cooling |
| Zone 5 | Chicago, Denver, Boston | 0 °F | 40,000 | 49,000 | Heating |
| Zone 6 | Minneapolis, Burlington VT | -10 °F | 36,000 | 56,000 | Heating |
| Zone 7 | Duluth, northern Maine | -20 °F | 32,000 | 63,000 | Heating |
2,000 sq ft, average insulation, 8 ft ceilings, the same load estimate as our BTU calculator.
Output Falls as It Gets Colder
A heat pump moves heat from outdoors, and the colder the air, the less it can move. Spec sheets give heating output at two test points, 47 °F and 17 °F. Across nine single-stage ratings we checked from GrandAire, Heil and Intertherm, the 17 °F output was 53% to 63% of the 47 °F figure, 57% on average. So a 3.5-ton unit that makes 42,000 BTU/h at 47 °F makes about 23,940 at 17 °F and roughly 13,706 at 0 °F, a third of the number on the box.
That is why the size on the quote doesn’t answer the winter question. The chart in the full plan above shows the two lines: heat loss climbing as it gets colder, output falling. Where they cross is the balance point.
The Balance Point and the Backup
Above the balance point the heat pump carries the house alone and cycles off now and then. Below it, something else has to fill the gap. For the default house that point is about 26 °F, and on a 0 °F night the gap is 35,294 BTU/h, or 10.3 kW.
Electric strips in the air handler are the usual backup. They come in 5, 8, 10, 15 and 20 kW sizes, and Manual S’s supplemental heat rule asks for 0.95 to 1.75 times the gap, so this house gets 10 kW. Strips turn each kW into 3,412 BTU/h and no more. The GrandAire sheet lists a COP of about 3.6 at 47 °F and 2.4 at 17 °F for its heat pumps, meaning 3.6 and 2.4 times as much heat per kW, so a system that leans on its strips for weeks shows up on the bill. They also need a big circuit: 10 kW at 240 V draws about 42 A, and because heat is a continuous load the circuit is sized at 125% of that, 52 A. Our wire size calculator picks the wire for it.
The other route is dual fuel: keep the furnace and let the thermostat switch to it below a set temperature. Below the switch point the furnace carries the whole load, so it still has to be sized for the design day.
Cold-Climate Heat Pumps Change the Rules
To be called cold-climate under ENERGY STAR or NEEP, a heat pump must keep at least 70% of its 47 °F output at 5 °F with a COP of at least 1.75. At that minimum, the same 3.5 tons makes about 27,900 BTU/h at 0 °F instead of 13,706, and the balance point drops from 26 °F to 20 °F. Many listed models do better than the minimum, which is why the calculator lets you enter a real one.
The sizing rules moved with the equipment. Manual S 2023 lets a variable-capacity heat pump go to 130% of the cooling load, against 115% for single-speed, so it can be sized up to cover more of the winter. For the default house that is 4 tons, about 31,886 BTU/h at 0 °F with a 16 °F balance point and 5 kW of strips. PNNL’s guide frames the choice as four approaches, from sizing for cooling alone to covering the whole heating load; in its Minneapolis example the balance point runs from 40 °F down to −15 °F across the four.
Why Bigger Isn’t Safer
An oversized heat pump reaches the thermostat setting quickly and shuts off, so it runs short cycles. In summer that leaves moisture in the air, because the coil never runs long enough to pull it out, and the house feels clammy at the right temperature. That is why the cooling limit exists, and why the table in the full plan marks sizes that pass it. Variable-capacity units get more room because they can slow down instead of cycling, but Manual S still wants their lowest output under 80% of the heat loss, so check the minimum capacity on the spec sheet as well as the maximum.
Ducted, Ductless and Mini-Splits
This calculator sizes the whole house. With ductless heads, each zone is sized on its own room loads, and a head too big for its room short-cycles like any oversized unit. Going ducted on old ductwork, check that the ducts can carry the new unit’s airflow, about 400 CFM per ton: our duct size calculator checks a duct you already have. A return that is too small is a common reason a new heat pump underperforms.
When to Get a Manual J
The loads here come from floor area, climate zone and an insulation level. They can’t see your window area, which way the house faces, air leaks or a finished basement. A Manual J room-by-room calculation can. Use this page to check that a quote is in the right range and to see what the winter will look like; when you have a Manual J, enter its numbers under “I have a load calculation”.
Heat Pump Size Questions
Loads use the same rule-of-thumb model as our BTU calculator. The output lines come from published single-stage spec sheets and the ENERGY STAR and NEEP cold-climate minimums; sizing limits and the backup rule come from Manual S 2023 as set out in ACCA’s 2025 public-review addendum. We test the engine on the worked examples above and on more than 9,000 combinations of zone, area, insulation, ceiling and heat pump type.
- PNNL Building America Solution Center: cold climate heat pump sizing and selection
- ENERGY STAR: air source heat pump key product criteria (cold climate)
- NEEP: cold climate air-source heat pump specification
- ACCA: proposed addendum c to Manual S 2023 (size limits, supplemental heat)
- ACCA blog: correctly sizing variable-capacity heat pumps (80% minimum capacity)
- GrandAire: WPH4 package heat pump ratings at 47 °F and 17 °F
- Heil: PHJ4 package heat pump ratings
- Intertherm / Revolv: HSH4ME heat pump ratings
- BPA PTCS: heat pump sizing reference guide (balance point)
- DOE Building America: climate zone lookup
Written and checked by Kris Lynch. Not reviewed by a licensed professional. See our methodology. Spotted a problem? Tell us. Updates: Nov 2026, launched.