Heat Pump Size Calculator

A 2,000 sq ft house in a zone 5 climate like Chicago needs a 3.5-ton heat pump for summer, but on a 0 °F night that unit covers only 28% of the heat loss, so it needs 10 kW of backup below about 26 °F. Enter your home below to see both seasons.

Heat pump size calculator

Look up your zone by ZIP (DOE)
I have a load calculation (Manual J)

Fill both and they replace the estimate. Use the design temperature from the same report.

Check a model from its spec sheet

Use maximum capacity. The NEEP cold-climate list gives all of these for listed models; spec sheets give 47 °F and 17 °F.

Enter the floor area.

One Unit, Two Loads

An air conditioner is sized for summer and a furnace for winter. A heat pump does both jobs with one compressor, so it has one size and two loads to meet. The default house above, 2,000 sq ft with average insulation in zone 5, gains 40,000 BTU/h on a hot day and loses 49,000 BTU/h on a 0 °F night. Size it for summer and it is short in winter; size it for winter and it is oversized all summer.

Which load is bigger depends on where you live. With the same house, summer wins in zones 1 to 4 and winter wins from zone 5 north:

ZoneExample citiesDesign dayHeat gain (BTU/h)Heat loss (BTU/h)Bigger load
Zone 1Miami, Honolulu45 °F60,00017,500Cooling
Zone 2Houston, Phoenix, Orlando30 °F54,00028,000Cooling
Zone 3Atlanta, Dallas, Los Angeles22 °F50,00033,600Cooling
Zone 4Washington DC, St. Louis, Seattle12 °F44,00040,600Cooling
Zone 5Chicago, Denver, Boston0 °F40,00049,000Heating
Zone 6Minneapolis, Burlington VT-10 °F36,00056,000Heating
Zone 7Duluth, northern Maine-20 °F32,00063,000Heating

2,000 sq ft, average insulation, 8 ft ceilings, the same load estimate as our BTU calculator.

Output Falls as It Gets Colder

A heat pump moves heat from outdoors, and the colder the air, the less it can move. Spec sheets give heating output at two test points, 47 °F and 17 °F. Across nine single-stage ratings we checked from GrandAire, Heil and Intertherm, the 17 °F output was 53% to 63% of the 47 °F figure, 57% on average. So a 3.5-ton unit that makes 42,000 BTU/h at 47 °F makes about 23,940 at 17 °F and roughly 13,706 at 0 °F, a third of the number on the box.

That is why the size on the quote doesn’t answer the winter question. The chart in the full plan above shows the two lines: heat loss climbing as it gets colder, output falling. Where they cross is the balance point.

The Balance Point and the Backup

Above the balance point the heat pump carries the house alone and cycles off now and then. Below it, something else has to fill the gap. For the default house that point is about 26 °F, and on a 0 °F night the gap is 35,294 BTU/h, or 10.3 kW.

Electric strips in the air handler are the usual backup. They come in 5, 8, 10, 15 and 20 kW sizes, and Manual S’s supplemental heat rule asks for 0.95 to 1.75 times the gap, so this house gets 10 kW. Strips turn each kW into 3,412 BTU/h and no more. The GrandAire sheet lists a COP of about 3.6 at 47 °F and 2.4 at 17 °F for its heat pumps, meaning 3.6 and 2.4 times as much heat per kW, so a system that leans on its strips for weeks shows up on the bill. They also need a big circuit: 10 kW at 240 V draws about 42 A, and because heat is a continuous load the circuit is sized at 125% of that, 52 A. Our wire size calculator picks the wire for it.

The other route is dual fuel: keep the furnace and let the thermostat switch to it below a set temperature. Below the switch point the furnace carries the whole load, so it still has to be sized for the design day.

Cold-Climate Heat Pumps Change the Rules

To be called cold-climate under ENERGY STAR or NEEP, a heat pump must keep at least 70% of its 47 °F output at 5 °F with a COP of at least 1.75. At that minimum, the same 3.5 tons makes about 27,900 BTU/h at 0 °F instead of 13,706, and the balance point drops from 26 °F to 20 °F. Many listed models do better than the minimum, which is why the calculator lets you enter a real one.

The sizing rules moved with the equipment. Manual S 2023 lets a variable-capacity heat pump go to 130% of the cooling load, against 115% for single-speed, so it can be sized up to cover more of the winter. For the default house that is 4 tons, about 31,886 BTU/h at 0 °F with a 16 °F balance point and 5 kW of strips. PNNL’s guide frames the choice as four approaches, from sizing for cooling alone to covering the whole heating load; in its Minneapolis example the balance point runs from 40 °F down to −15 °F across the four.

Why Bigger Isn’t Safer

An oversized heat pump reaches the thermostat setting quickly and shuts off, so it runs short cycles. In summer that leaves moisture in the air, because the coil never runs long enough to pull it out, and the house feels clammy at the right temperature. That is why the cooling limit exists, and why the table in the full plan marks sizes that pass it. Variable-capacity units get more room because they can slow down instead of cycling, but Manual S still wants their lowest output under 80% of the heat loss, so check the minimum capacity on the spec sheet as well as the maximum.

Ducted, Ductless and Mini-Splits

This calculator sizes the whole house. With ductless heads, each zone is sized on its own room loads, and a head too big for its room short-cycles like any oversized unit. Going ducted on old ductwork, check that the ducts can carry the new unit’s airflow, about 400 CFM per ton: our duct size calculator checks a duct you already have. A return that is too small is a common reason a new heat pump underperforms.

When to Get a Manual J

The loads here come from floor area, climate zone and an insulation level. They can’t see your window area, which way the house faces, air leaks or a finished basement. A Manual J room-by-room calculation can. Use this page to check that a quote is in the right range and to see what the winter will look like; when you have a Manual J, enter its numbers under “I have a load calculation”.

Heat Pump Size Questions

With average insulation, about 3 tons in a zone 4 climate such as Washington DC or St. Louis, and 2.5 tons in zone 5 (Chicago, Denver, Boston), where it needs help below about 27 °F. In zone 2 (Houston, Phoenix) the bigger summer load pushes it to 3.5 tons.

About 4 tons in zone 4 and 3.5 tons in zone 5, both with average insulation. In zone 6 (Minneapolis) the summer load is smaller, so cooling only allows 3 tons, and a standard model then needs 15 kW of backup on the coldest nights.

Not reliably. The same 2,000 sq ft in zone 5 comes out at 4 tons with 20 kW of backup when it is drafty and poorly insulated, and 2.5 tons with 5 kW when it is tight and well insulated. Insulation and climate move the answer more than the floor area does.

It still runs, with less output. A typical standard single-stage unit, on our 57% at 17 °F line, makes about 33% of its 47 °F rating at 0 °F. A cold-climate model at the ENERGY STAR minimum keeps about 66%, and many listed models hold more. The question is whether that covers your heat loss.

Take the heat loss on the design day, subtract the heat pump’s output at that temperature, and divide by 3,412. For the default house that is (49,000 − 13,706) ÷ 3,412 = 10.3 kW, so a 10 kW strip. A 10 kW strip on 240 V draws about 42 A, so check the circuit with our wire size calculator.

Yes, that is a dual-fuel system. The thermostat switches to the furnace below a set outdoor temperature, often close to the balance point, which is about 26 °F for the default house. Below that the furnace carries the whole load on its own, 49,000 BTU/h on the design day, so it must still be big enough.

Where summers dominate, size for cooling. With our default house, the heat loss is bigger than the heat gain only in zones 5 to 7, so from Chicago north the question is how much backup you accept. Manual S 2023 lets variable-capacity units go to 130% of the cooling load to cover more of the winter.

Loads use the same rule-of-thumb model as our BTU calculator. The output lines come from published single-stage spec sheets and the ENERGY STAR and NEEP cold-climate minimums; sizing limits and the backup rule come from Manual S 2023 as set out in ACCA’s 2025 public-review addendum. We test the engine on the worked examples above and on more than 9,000 combinations of zone, area, insulation, ceiling and heat pump type.

Written and checked by Kris Lynch. Not reviewed by a licensed professional. See our methodology. Spotted a problem? Tell us. Updates: Nov 2026, launched.