Duct Size Calculator

A bedroom run carrying 100 CFM needs a 6 in. round metal duct at the usual 0.10 friction rate, or 7 in. if it’s flex with some slack. Enter your airflow below for the size, the limit that set it and, for returns, the filter grille.

Duct size calculator

Room airflow comes from a heat load. Don’t know it? Our BTU calculator gives the load; a common rule is 400 CFM per ton of cooling.

Settings and prices (optional)

The friction rate is the pressure the blower has left after the coil, filter and grilles, spread over the longest run. A Manual D design works it out; 0.10 in. w.c. per 100 ft is the usual ductulator setting.

Enter the airflow the duct has to carry.

Two Limits Size Every Duct, and They Swap Over

A ductulator gives you a diameter from two numbers, the airflow and a friction rate. That covers half of the job. ACCA’s Manual D also caps how fast air may move: 900 feet per minute in supply ducts and 700 in returns, because faster air is louder and throws off the fitting losses the design relies on. Every duct has to pass both tests, and which one decides the size depends on how big the duct is.

Take a 3-ton system moving 1,200 CFM. At 0.10 in. w.c. per 100 ft, friction alone asks for a 14.89 in. duct. On the supply side, keeping the air under 900 fpm needs 15.64 in., so the trunk is 16 in. On the return side, 700 fpm needs 17.73 in., so the return is 18 in. A 16 in. return would carry the air at 859 fpm, and you would hear it at the grille.

At the 0.10 setting, friction decides supply ducts up to 12 in., and speed decides from 14 in. up; the switch comes at about 805 CFM. Returns switch much sooner: from 9 in. up, which is anything over about 290 CFM, speed decides. So a single bedroom run is a friction problem, while nearly every return and any trunk past 2 tons is a speed problem. The result above tells you which one set your size, and the full plan lists both limits for every stock size.

Where the Friction Rate Comes From

The friction rate is not a property of the duct. It is the blower’s leftover pressure, after the coil, filter, grilles and dampers have taken their share, spread over the longest run including the equivalent length of every fitting: available pressure × 100 ÷ total effective length. A system with long runs and lots of elbows ends up with a low rate, which means bigger ducts everywhere.

0.10 became the default because slide ductulators print a residential setting there, as ACHR News points out, not because most houses work out to it. Change it and the sizes move. A 100 CFM bedroom run is 6 in. at 0.10 and 7 in. at 0.06. If a contractor has done a Manual D for your house, enter their rate under “Settings and prices” and the sizes will match their design.

Flex Duct: How It’s Hung Changes the Size

Flex duct pulled tight and strapped performs close to metal. The Texas A&M tests that Energy Vanguard wrote up found the curves for the two almost on top of each other at full stretch. The trouble is slack. Under the Air Diffusion Council’s installation standard, flex compressed 15% has about twice the friction, and at 30% it can reach four times.

For the same 100 CFM bedroom run, that turns a 6 in. duct into 7 in. with some slack and 8 in. when it sags between the joists. Compression is measured against the duct’s fully stretched length, so 15% means a 16 ft length of flex squeezed into a 13.6 ft run, with the extra bunched into the bends and sags. Pick how yours is hung, or use “Check a duct I have” to see what an existing flex run really carries.

Rectangular Ducts and Joist Bays

A rectangle has more wall around the same air than a circle, so it must be bigger than the round duct it replaces. The Huebscher formula converts one to the other. To do the job of that 1,200 CFM trunk in an 8 in. joist depth, you need 26×8 in.: it works like a 15.1 in. round for friction, and its 208 sq in. opening stays under the 900 fpm limit, which needs at least 192. Manual D study guides keep the long side no more than 4 times the short side; flatter than that and friction, heat loss and drumming all rise.

Sizing the Return Side

The ICC’s own commentary on the code notes that supply ducts are rarely the problem, while undersized returns turn up often, particularly on heat pumps. The lower 700 fpm limit is why returns come out a size or two bigger than the supply for the same airflow. The grille needs the same care. Hart & Cooley’s rule of thumb is 2 CFM per sq in. of filter, which keeps the air through a filter grille under the 300 fpm ACCA recommends. A 3-ton system therefore wants about 600 sq in. of filter, a 20×30, and a single 16×25 grille (400 sq in.) handles only 800 CFM. A return grille you can hear is the usual sign this side is short; Contracting Business notes that air through a grille above about 500 fpm is easy to hear.

What This Calculator Can’t Tell You

It sizes one run at one friction rate. It doesn’t know your room loads; that comes from a Manual J calculation, and our BTU calculator is a starting point. It can’t see leaks either, and a well-sized duct with open seams still delivers less air than it should.

Exhaust ducts follow their own rules, not this friction method. At my place I installed a dryer vent, which meant making a hole through a limestone wall and hooking the vent and the exhaust duct up to it. A dryer duct isn’t sized at all: the code fixes it at 4 in. and limits the run to 35 ft, minus 5 ft for each 90° bend and 2.5 ft for each 45°, unless the dryer maker’s instructions allow more. Bathroom fan ducts use a separate code table, and our bathroom exhaust fan calculator checks them.

Duct Size Questions

At 0.10 in. w.c. per 100 ft, a 10 in. round supply duct. A return carrying the same 400 CFM goes up to 12 in., because in a 10 in. duct the air moves at 733 fpm, over the 700 fpm return limit. Energy Vanguard’s worked example also lands on a 12 in. return for 400 CFM.

About 109 CFM in round metal at 0.10, or 97 at 0.08. For comparison, 4 in. carries about 37, 5 in. about 67 and 8 in. about 232 at 0.10. A 6 in. flex duct with roughly 15% slack drops to about 75 CFM.

2 tons is about 800 CFM at 400 CFM per ton. That needs a 14 in. round supply trunk, a 16 in. return and a 20×20 filter grille (400 sq in. of filter at 2 CFM per sq in.). The branches off the trunk are sized one room at a time.

Yes, if together they carry the airflow. Two 12 in. ducts carry about 1,356 CFM by friction at 0.10 against 1,450 for one 16 in., and at the 900 fpm supply limit each 12 in. takes 707 CFM, so the pair handles a 1,200 CFM trunk. Two runs mean more metal and more fittings to seal.

For bare round metal, wrap a tape around it and divide by 3.14: a duct that measures 19 in. around is 6 in. across. Insulated flex is bigger outside than its inner core, so measure the core at a joint or read the size printed on the jacket. A 6 in. flex can measure 8 in. or more across its insulation.

Not directly. Section M1601.1 of the 2021 International Residential Code says ducts are to be installed following ACCA Manual D, the equipment maker’s instructions or another approved method. The ICC commentary adds that undersized returns are often found in the field, especially on heat pumps.

The friction equation and the rectangle conversion are from Engineering ToolBox, the speed limits from ACCA Manual D as reported by Energy Vanguard and Contracting Business, the flex factors from the ADC standard, and the grille rule from Hart & Cooley. We test the engine on the worked examples above and on more than 130,000 combinations of airflow, duct type, role and friction rate.

Written and checked by Kris Lynch. Not reviewed by a licensed professional. See our methodology. Spotted a problem? Tell us. Updates: Nov 2026, launched.